|a Bendiš, Rafaela
|9 34928
|
| 245 |
|
|
|a Analitičko određivanje granične pogreške strujnog mjernog transformatora :
|b diplomski rad /
|c Rafaela Bendiš ; [mentor Ivan Leniček].
|
| 246 |
1 |
|
|a Analytical determination of measuring current transformer limits of error
|i Naslov na engleskom:
|
| 260 |
|
|
|a Zagreb,
|b R. Bendiš,
|c 2014.
|
| 300 |
|
|
|a 73 str. ;
|c 30 cm +
|e CD-ROM
|
| 520 |
3 |
|
|a Sažetak na hrvatskom: U ovom diplomskom radu je trebalo analitički odrediti graničnu pogrešku strujnog mjernog transformatora. Za strujni mjerni transformator koji ima 1500 amperzavoja i odvojke primara nazivnih struja 50, 75, 100 i 150 A, te nazivnu struju sekundara 1 A su napravljena laboratorijska mjerenja gdje su za svaki odvojak primara, točnije za svaki prijenosni omjer, posebnim metodama određeni elementi nadomjesne sheme transformatora. Također su, za svaki prijenosni omjer i nazivnu struju sekundarnog namota od 1 A, napravljeni Mӧllinger - Geweckeovi dijagrami iz kojih je proračunata strujna i fazna pogreška transformatora. Na kraju, napravljeno je dodatno mjerenje Swerlein metodom, te proračun pogreške i mjerne nesigurnosti laboratorijskog postupka. Za slučaj obrađen laboratorijskim mjerenjem, i analitički je proračunata pogreška transformatora, te su uspoređeni rezultati. Rezultati dobiveni mjerenjem su potvrdili rezultate analitičkog postupka.
|
| 520 |
3 |
|
|a Sažetak na engleskom: The purpose of this thesis is to analytically determine marginal error for the selected current transformer. Current transformer has 1500 ampere-turns and sections with primary winding for nominal currents of 50, 75, 100 and 150 A and its nominal secondary winding current is 1 A. Specific measurement methods were used for every selected transmission ratio and for determined elements of current transformer’s equivalent circuit. For every selected transmission ratio and nominal secondary current are plotted Möllinger - Gewecke diagrams. With those diagrams we could analytically determine current and phase errors of current transformer. And finally, additional Swerlein method measurement is done. From laboratory measurement, error and its measurement uncertainty are compared with analytically determined error for that instance. Results that were done analytically are confirmed by measurement results.
|
| 653 |
|
1 |
|a strujni mjerni transformator
|a otpor namota
|a impedancija jezgre transformatora
|a struja magnetiziranja
|a rasipni induktivitet
|a mjerna nesigurnost
|a granična pogreška
|a strujna pogreška
|a fazna pogreška
|a Möllinger – Geweckeov dijagram
|
| 653 |
|
1 |
|a current transformer
|a winding resistance
|a magnetizing impedance
|a magnetizing current
|a leakage inductance
|a measurement uncertainty
|a marginal error
|a current error
|a phase error
|a Möllinger – Gewecke diagram
|