1 |
|
|a Baklaić, Anja
|9 34916
|
245 |
|
|
|a Dimenzioniranje izolacijskih sustava u SF6 plinom izoliranim postrojenjima :
|b diplomski rad /
|c Anja Baklaić ; [mentor Željko Štih].
|
246 |
1 |
|
|a Dimensioning of isolating systems in SF6 gas insulated substations
|i Naslov na engleskom:
|
260 |
|
|
|a Zagreb,
|b A. Baklaić,
|c 2014.
|
300 |
|
|
|a 93 str. ;
|c 30 cm +
|e CD-ROM
|
520 |
3 |
|
|a Sažetak na hrvatskom: Električno polje se formira u izolaciji između električnih naboja smještenih na površini elektroda u kojoj djeluju električne sile. Elektrostatsko polje je definirano kao polje koje je uzrokovano mirnim nabojem na površini elektroda, i unutar kojeg nema slobodnog naboja u prostoru. U ovom radu računa se statičko električno polje u GIS prekidaču. Glavna značajka GIS postrojenja je potpuno oklapanje dijelova pod naponom metalnim plaštem gdje prethodno definirani SF_6 plin služi i kao izolaciono sredstvo i kao sredstvo za gašenje električnog luka. Sumporov heksafluorid (SF_6) je neotrovan, neagresivan, kemijski stabilan plin pri atmosferskom tlaku i temperaturi < 500⁰C, bez boje i mirisa. Ovaj plin ne postoji u prirodi, nego se dobiva direktnom sintezom fluora i tekućeg sumpora egzotermnom reakcijom u posebnim postrojenjima. osnovna svojstva koja su mu omogućila upotrebu i osigurala vodeće mjesto u prekidačima visokog napona jesu: velika gustoća, elektronegativnost, dobra toplinska vodljivost i mala vremenska konstanta luka. Pri proračunu statičkih električnih polja i dimenzioniranju izolacije potrebno je poznavati brojne pojave i utjecaje na napon preskoka/proboja u plinu kao što su: napon pojave korone, površinske nesavršenosti (hrapavost) elektroda, čestice prašine u plinu, kombinacija plina i izolatora od krutog materijala i prisutnost vlage. Proračuni polja se izvode u programu Maxwell. Maxwell je simulacijski program elektromagnetskog polja namijenjen za elektroinženjere zadužene za projektiranje i 3-D i 2-D analizu elektromagnetskih i elektromehaničkih uređaja.
|
520 |
3 |
|
|a Sažetak na engleskom: The electric field is formed in the isolation between electric charges located on the surface of the electrode in which they operate electric power. Electrostatic field is defined as a field that is caused by peaceful charge on the surface of electrodes, and within which there is no free charge in the area . In this paper we calculated the static electric field in GIS. The main feature of the GIS facility is completely shielding parts energized metal mantle where previously defined SF_6 gas is used as the insulating agent and as a means of extinguishing the arc. Sulfur hexafluoride (SF_6) is non-toxic, non-aggressive, chemically stable gas at atmospheric pressure and temperatures < 500 ⁰ C, colorless and odorless . This gas does not exist in nature, but is obtained by direct synthesis of fluorine and sulfur exothermic reaction liquid in a plant. Basic properties that enabled him to use and secure a leading position in the high-voltage circuit breakers are: high density, electronegativity , good thermal conductivity and a small time constant arc. For calculations of the static electric field and the dimensioning of insulation is necessary to know the number of occurrence and effects of the flashover/breakdown voltage in a gas such as: the occurrence of voltage corona, surface imperfections (roughness) of electrodes, the dust particles in a gas, a combination of gas and solid material of the insulator, and the presence of moisture. Field calculations are performed in Maxwell. Maxwell is electromagnetic field simulation program designed for 3 - D and 2 - D analysis of electromagnetic and electromechanical devices .
|
653 |
|
1 |
|a Statičko električno polje
|a SF_6 plin
|a plinom izolirani prekidač
|a napon preskoka
|a napon proboja
|a Maxwell
|
653 |
|
1 |
|a Static electric field
|a SF_6 gas
|a gas-insulated switchgear
|a voltage flashover
|a voltage breakdown
|a Maxwell
|